Voltage drop calculator
Single-phase and three-phase voltage drop for copper and aluminium cable, in AWG or mm², with the smallest standard size that stays within the drop you choose. The formula is shown, nothing leaves this page.
Nothing leaves this page. Length is the one-way distance from the supply to the load.
All standard sizes for these inputs
| Size | Area, mm² | Resistance of one conductor, Ω | Drop, V | Drop, % | Within limit? |
|---|
The formulas
Single-phase / DC: V_drop = 2 · ρ · L · I / A Three-phase: V_drop = √3 · ρ · L · I / A % drop = V_drop / V_supply × 100 ρ resistivity, Ω·mm²/m (copper 0.0172, aluminium 0.0282, both at 20 °C) L one-way length, m I current, A A conductor area, mm² Temperature: ρ(T) = ρ20 · (1 + α · (T − 20)), α = 0.00393 (Cu), 0.00403 (Al) per °C
This is the resistive, steady-state approximation: it ignores cable reactance, power factor, skin effect, bundling and start-up surges, which matter on large conductors, long runs and motor loads. AWG areas are the standard values from the AWG diameter formula; metric sizes are the preferred cross-sections of IEC 60228.
This page does not give ampacity (current-carrying capacity) or permitted drop limits. Both depend on the installation method, insulation, ambient temperature, grouping and your local electrical code. The 3% default is only a starting value you can change. Check the local code and the cable maker's data for both.
Planning aid; verify against local code and the manufacturer's data; the qualified person on site is responsible.