HVAC calculators
Capacity, airflow and temperature converters, airflow from capacity, round and rectangular duct sizing, superheat and subcooling arithmetic, and a rough room load. Rules of thumb are labelled as such.
Planning aid; verify against local code and the manufacturer's data; the qualified person on site is responsible. Nothing leaves this page.
Unit converters
Type in any box in a row; the others follow. 1 ton of cooling = 12,000 BTU/h = 3.517 kW.
Airflow from capacity
CFM = BTU/h ÷ (1.08 × ΔT °F). The 1.08 factor assumes standard air (about sea-level density, 0.075 lb/ft³); at altitude or high temperature the true flow for the same capacity is higher.
400 CFM per ton is a rule of thumb for typical comfort cooling, not a design value. Humid climates often use less, dry climates more. Use the equipment maker's data for the actual unit.
Round duct sizing
By velocity: area = CFM ÷ velocity. By friction rate: the ASHRAE round-duct equation for galvanised steel and standard air, Δp = 0.109136 · CFM1.9 ÷ D5.02 (Δp in in. w.g. per 100 ft, D in inches), solved for D. Real ducts differ with material, fittings and air density, so round up to a stocked size and check with your own duct calculator or the equipment's static-pressure data.
Rectangular duct: equivalent round diameter
De = 1.3 · (a·b)0.625 ÷ (a+b)0.25 (ASHRAE, equal friction and flow). It gives the round duct with the same friction loss at the same airflow, not the same area.
Superheat and subcooling
This page contains no refrigerant pressure-temperature data. Read the saturation (dew or bubble point) temperature for your refrigerant from your gauge set's scale, a digital manifold or the refrigerant's own chart, then enter it here together with the measured line temperatures.
Superheat = suction line temperature − evaporator saturation temperature. Subcooling = condenser saturation temperature − liquid line temperature. Differences are the same number in °F or K, so use one unit throughout. Target values come from the equipment's data plate or manufacturer's charging chart, not from this page.
Rough room cooling load
Rule of thumb, not a Manual J load calculation. It cannot see insulation, glazing, orientation, infiltration or climate. Use it for a first idea only; size equipment from a proper load calculation.
Load = (area × base + people × W + equipment W) × 3.412 BTU/h per W where watts apply, then × (1 + extra %). The defaults are common rough figures, not standards; change them to match your own experience.